Water

The water withdrawal and return flows from energy technologies are calculated in MESSAGE following the approach described in Fricko et al., (2016) [18]. Each technology is prescribed a water withdrawal and consumption intensity (e.g., m3 per kWh) that translates technology outputs optimized in MESSAGE into water requirements and return flows.

../_images/ppl_energy_balance.png

Fig. 30 Simplified power plant energy balance.

For power plant cooling technologies, the amount of water required and energy dissipated to water bodies as heat is linked to the parameterized power plant fuel conversion efficiency (heat rate). Looking at a simple thermal energy balance at the power plant (Fig. 30), total combustion energy (\(E_{comb}\)) is conveterted into electricity (\(E_{elec}\)), emissions (\(E_{emis}\)) and additional thermal energy that must be absorbed by the cooling system (\(E_{cool}\)):

\(E_{comb} = E_{elec} + E_{emis} + E_{cool}\)

Converting to per unit electricity, we can estimate the cooling required per unit of electricity generation (\(\phi_{cool}\)) based on average heat-rate (\(\phi_{comb}\)) and heat lost to emissions (\(\phi_{emis}\)), and this data is identified from the literature [18].

\(\phi_{cool} = \phi_{comb} - \phi_{emis} - 1\)

With time-varying heat-rates (i.e., \(t =0,1,2,...\)) and a constant share of energy to emissions and electricity:

\(\phi_{cool}[t] = \phi_{comb}[t] \cdot \left( \, 1 - \dfrac{\phi_{emis}}{\phi_{comb}[0]} \, \right) - 1\)

Increased fuel efficiency (lower heat-rate) reduces the cooling requirement per unit of electricity generated. This enables heat rate improvements for power plants represented in MESSAGE to be translated into improvements in water intensity. Water withdrawal and consumption intensities for power plant cooling technologies are calibrated to the range reported in Meldrum et al., (2013) [59]. Additional parasitic electricity demands from recirculating and dry cooling technologies are accounted for explicitly in the electricity balance calculation. All other technologies follow the data reported in Fricko et al. (2016) [18].

A key feature of the implementation is the representation of power plant cooling technology options for individual power plant types (Fig. 31). Each power plant type that requires cooling in MESSAGE is connected to a corresponding cooling technology option (once-through, recirculating or air cooling), with the investment into and operation of the cooling technologies included in the optimization decision variables [70]. This enables MESSAGE to choose the type of cooling technology for each power plant type and track how the operation of the cooling technologies impact water withdrawals, return flows, thermal pollution and parasitic electricity use.

../_images/cooling_implement1.png

Fig. 31 Implementation of cooling technologies in the MESSAGE IAM.

Costs and efficiency for cooling technologies are estimated following previous technology assessments [50, 114, 115]. The initial distribution of cooling technologies in each region and for each technology is estimated with the dataset described in Raptis and Pfister (2016) [82]. The shares estimated at the river basin-scale are depcited in Fig. 32 .

../_images/cooling_implement2.png

Fig. 32 Average cooling technology shares across all power plant types at the river basin-scale.